Guaranteeing the trouble-free operation of capacitor banks in power-supply systems of industrial enterprises

Репозиторій DSpace/Manakin

Показати простий запис статті

dc.contributor.author Gapon, D.A.
dc.contributor.author Bederak, Ya.S.
dc.date.accessioned 2019-02-13T11:56:48Z
dc.date.available 2019-02-13T11:56:48Z
dc.date.issued 2016
dc.identifier.citation Guaranteeing the trouble-free operation of capacitor banks in power-supply systems of industrial enterprises / D.A. Gapon, Ya.S. Bederak // Електротехніка і електромеханіка. — 2016. — № 1. — С. 56-58. — Бібліогр.: 9 назв. — англ. uk_UA
dc.identifier.issn 2074-272X
dc.identifier.other DOI: https://doi.org/10.20998/2074-272X.2016.1.10
dc.identifier.uri http://dspace.nbuv.gov.ua/handle/123456789/147039
dc.description.abstract Purpose. The problem of resonance phenomena in power systems of industrial enterprises using capacitor banks for reactive power compensation was detected. Circuit of the capacitor banks tier to downshift main substation tires is present. But there is no common algorithm to calculate and avoid such trouble. The main goal of this article is to introduce some basics for power supply systems with possible resonant circuits engineering. Methodology. At the first step the data on the change of the current in the chemical company network when changing capacitor banks value are received. For these purposes the oscilloscope function of digital protection relay was used. Current data samples were analyzed by spectrum detection software. Most significant levels of the 3rd and 5th harmonics were achieved. Comparison of harmonic distortion levels with and without capacitor bank is given. Results. Achieved data allow making conclusion about overloading reasons of capacitor banks while higher harmonics currents presence. A voltage and current harmonious composition measuring in the absence of power quality analyzers using digital protection relay terminals or emergencies registers are proposed. The necessity of power quality monitoring near capacitor banks connections to avoid resonance phenomena (current and voltage resonance) in industrial power supply systems is proven. The control algorithm of capacitor banks to provide electromagnetic compatibility, while various modes of nonlinear load operation is given. Originality. Using of digital protection relay oscilloscoping for current resonant detection can allow to significally reduce time and cost of solution. Replacement parallel circuit comprising a branch and one active-inductive load to another branch network in the presence of higher harmonics source are proposed. Practical value. A sequence for measuring the levels of harmonic components at the connections of capacitor banks in the absence of specialized instruments is proposed. The algorithm to avoid possible resonance currents in the presence of condensing units is proposed. uk_UA
dc.description.abstract В статье рассматривается проблема резонансных явлений в системах электроснабжения промышленных предприятий, использующих конденсаторные установки для компенсации реактивной мощности. Приведены данные по изменению токов 3-й и 5-й гармонических составляющих в сети химического предприятия при изменении мощности присоединенных конденсаторных установок. Предложен способ измерения качества электроэнергии при отсутствии анализаторов. Разработан алгоритм обеспечения электромагнитной совместимости на присоединениях конденсаторных установок uk_UA
dc.language.iso en uk_UA
dc.publisher Інститут технічних проблем магнетизму НАН України uk_UA
dc.relation.ispartof Електротехніка і електромеханіка
dc.subject Електричні станції, мережі і системи uk_UA
dc.title Guaranteeing the trouble-free operation of capacitor banks in power-supply systems of industrial enterprises uk_UA
dc.type Article uk_UA
dc.status published earlier uk_UA
dc.identifier.udc 621.311